Operation Environment and Safety
2022-05-19
Operating Temperature Range:
Max. Range: -40℃~60℃ (See specific battery specifications)
Optimal Range: 25℃±5℃
Relative Humidity 5%-95% (should not reach Dew point temperature /no condensed water)
Altitude ≦ 4000m
Keep batteries away from any source of ignition, organic solvent, or direct sunlight;
Keep the consistent ambient temperature; the temperature difference between each battery of the same battery bank should be ≦3℃.